Basic multi function metering PM5350 Functions and characteristics cont PE86323 General Use on LV and MV systems b Basic metering with THD and min max readings b Instantaneous rms values Current Total Phases and neutral b Voltage Total Ph Ph and Ph N b Frequency b Real reactive and apparent power Total and per phase Signed True Power Factor Total and per phase Signed Four Quadrant

Transcription:

Basic multi function metering PM5350,Functions and characteristics cont. Use on LV and MV systems b,Basic metering with THD and min max readings b. Instantaneous rms values,Current Total Phases and neutral b. Voltage Total Ph Ph and Ph N b,Frequency b,Real reactive and Total and per phase Signed. apparent power, True Power Factor Total and per phase Signed Four Quadrant.
Displacement PF Total and per phase Signed Four Quadrant. Unbalanced I VL N VL L b,Energy values Stored in,non volatile. Accumulated Active Reactive and Apparent Energy Received Delivered b. Net and absolute,Demand values,Current average Present Last Predicted b. Peak Peak Date Time,Active power Present Last Predicted b. Peak Peak Date Time,Reactive power Present Last Predicted b. Peak Peak Date Time,Apparent power Present Last Predicted b.
Peak Peak Date Time, Peak demand with timestamping D T for current powers b b. Demand calculation Sliding fixed and rolling block b b. Synchronization of the measurement window b b,Other measurements. I O timer b b,Operating timer b b,Active load timer b b. PM5350 meter parts,Alarm counters b b,A Retainer clips Power quality measurements. B Control power supply connector THD thd Total Harmonic Distortion I VLN VLL. C Voltage inputs TDD thd Total Demand Distortion b. D Digital outputs Data recording,E Rs485 port COM1 b b.
Min max of instantaneous values plus phase,F Digital outputs identification. G Optical revenue switch Standard 29 Unary 4,Alarms with 1s timestamping. H Current inputs Digital 4,Alarms stored in non volatile memory 40 events b. Inputs Outputs,Digital inputs 4 DI1 DI2 DI3 DI4,Digital outputs 2 relay outputs DO1. White backlit LCD display 6 lines 4 concurrent values b. IEC or IEEE visualization mode b,Communication,Modbus RTU Modbus ASCII Jbus Protocol b.
Firmware update via RS485 serial port b,DLF3000 via the Schneider Electric website. www schneider electric com,Basic multi function metering PM5350. Functions and characteristics cont,Electrical characteristics. Type of measurement True rms up to the 15th harmonic on three phase. 32 samples per cycle zero blind,Measurement Current Phase 1 0 30. accuracy Voltage L N 1 0 30,Power Factor 1 0 005, Power Phase IEC 61557 12 Class 0 5 For 5 A nominal CT for 1.
A nominal CT when I 0 15A,0 5 from 0 25 A to 9 0 A at COS 1. 0 6 from 0 50 A to 9 0 A at COS 0 5 ind or cap,Frequency 1 0 05. Real Energy IEC 62053 22 Class 0 5S IEC 61557 12 Class 0 5. For 5 A nominal CT for 1 A nominal CT when I 0 15A. 0 5 from 0 25 A to 9 0 A at COS 1,0 6 from 0 50 A to 9 0 A at COS 0 5 ind or cap. IEC 61557 12 Class 0 5, Reactive Energy IEC 62053 23 Class 3 IEC 61557 12 Class 2. For 5 A nominal CT for 1 A nominal CT when I 0 15A. 2 0 from 0 25 A to 9 0 A at SIN 1,2 5 from 0 50 A to 9 0 A at SIN 0 5 ind or cap.
Data update rate 1 second nominal 50 60 cycles, Input voltage VT primary 1 0 MV AC max starting voltage depends on VT ratio. U nom 277 V L N, Measured voltage with IEC 20 to 480 V AC L L 20 to 277 V AC L N CAT III. overrange Crest FactorIEC 20 to 690 V AC L L 20 to 400 V AC L N CAT II. UL 20 to 300 V AC L L CAT III,Permanent overload 700 Vac L L 404 Vac L N. Impedance 10 M W, Front screen view of PM5350 Frequency range 45 to 70 Hz. Input current CT ratings Primary Adjustable 1 A to 32767 A. Secondary 1A 5 A nominal,Measured voltage with 5 mA to 9 A.
overrange Crest Factor, Withstand Continuous 20 A 10 sec hr 50 A 1 sec hr 500 A. Impedance 0 3 mW,Frequency range 45 to 70 Hz,Burden 0 024 VA at 9 A. AC control Operating range 85 265 V AC, Burden 4 1 VA 1 5 W typical 6 7 VA 2 7 W max at 120 V AC. 6 3 VA 2 0 W typical 8 6 VA 2 9 W max at 230 V AC,9 6 VA 3 5 W maximum at 265 V AC. Frequency 45 to 65 Hz, Ride through time 100 mS typical at 120 V AC and maximum burden.
400 mS typical at 230 V AC and maximum burden,DC control Operating range 100 to 300 V DC. power Burden 1 4 W typical 2 6 W maximum at 125 V DC. 1 8 W typical 2 7 W maximum at 250 V DC,3 2 W maximum at 300 V DC. Ride through time 50 mS typical at 125 V DC and maximum burden. Real time clock Ride through time 30 seconds,Digital output Number Type 2 Mechanical Relays. Output frequency 0 5 Hz maximum 1 second ON 1 second OFF. minimum times, Switching Current 250 V AC at 2 0 Amps 200 k cycles resistive. 250 V AC at 8 0 Amps 25 k cycles resistive,250 V AC at 2 0 Amps 100 k cycles COS 0 4.
250 V AC at 6 0 Amps 25 k cycles COS 0 4,30 V DC at 2 0 Amps 75 k cycles resistive. 30 V DC at 5 0 Amps 12 5 k cycles resistive,Isolation 2 5 kVrms. Status Digital Voltage ratings ON 18 5 to 36 V DC OFF 0 to 4 V DC. Inputs Input Resistance 110 k W,Maximum Frequency 2 Hz T ON min T OFF min 250 ms. Response Time 10 ms,Isolation 2 5 kVrms,Whetting output Nominal voltage 24 V DC. Allowable load 4 mA,Isolation 2 5 kVrms, 1 Measurements taken from 45 Hz to 65 Hz 0 5 A to 9 A 57 V to 347 V 0 5 ind to 0 5 cap.
power factor with a sinusoidal wave,Basic multi function metering PM5350. Functions and characteristics cont,Mechanical characteristics. Weight 250 g, IP degree of protection IEC 60529 IP51 front display IP30 meter body. Dimensions WxHxD 96 x 96 x 44 mm depth of meter from housing. mounting flange, 96 x 96 x 13 mm protrusion of meter from housing flange. Mounting position Vertical,Panel thickness 6 35 mm maximum.
Environmental characteristics,Operating Meter 25 C to 70 C. temperature,Display 20 C to 70 C, Display functions to 25 C with reduced performance. Storage temp Meter display 40 C to 85 C,Humidity rating 5 to 95 RH at 50 C non condensing. Pollution degree 2,Altitude 3000 m max,Electromagnetic compatibility. Electrostatic discharge IEC 61000 4 2 1,Immunity to radiated fields IEC 61000 4 3 1.
Immunity to fast transients IEC 61000 4 4 1,Immunity to impulse waves IEC 61000 4 5 1. Conducted immunity IEC 61000 4 6 1,Immunity to magnetic fields IEC 61000 4 8 1. Immunity to voltage dips IEC 61000 4 11 1, Radiated emissions FCC part 15 class A EN 55011 Class A. Conducted emissions FCC part 15 class A EN 55011 Class A. Harmonics IEC 61000 3 2 1,Flicker emissions IEC 61000 3 3 1. Europe e as per IEC 61010 1, U S and Canada cULus as per UL61010 1 IEC 61010 1 3rd Edition.
Measurement category Voltage and current Per IEC 61010 1. inputs CAT III 277 V L N 480 V L L nominal,CAT II 400 V L N 690 V L L nominal. Per UL 61010 1 and CSA C22 2 No 61010 1,CAT III 300 V L L. Overvoltage Category Control power CAT III,Dielectric As per IEC 61010 1. Double insulated front panel display,Protective Class II. Communication, RS 485 port 2 Wire 9600 19200 or 38400 baud Parity Even.
Odd None 1 stop bit if parity Odd or Even 2 stop bits if. None Modbus RTU Modbus ASCII 7 or 8 bit JBUS, Firmware and language file update Update via comunication port using DLF3000 software. Isolation 2 5 kVrms double insulated,Human machine interface. Display type Monochrome Graphics LCD,Resolution 128 x 128. Backlight White LED,Viewable area W x H 67 x 62 5 mm. Keypad 4 button,Indicator Heartbeat Comm activity Green LED.
Energy pulse output Active alarm indication configurable. Type Optical amber LED,Wavelength 590 to 635 nm,Maximum pulse rate 2 5 kHz. 1 As per IEC 61557 12,Basic multi function metering PM5350 Power Meter. Dimensions and connection,Rear of meter open,Rear view retainers installation. For detailed installation instructions see the product s Installation guide. Basic multi function metering PM5350 Power Meter,Dimensions and connection cont. Rear view retainers users, For detailed installation instructions see the product s Installation guide.